Boiler & Radiator Sizing Calculator
Estimate how much heat a room or home loses on a cold design day, what size radiators that means at different flow temperatures, and a starting range for boiler output.
Your property
What do you want to size?
Builds a simple box model of your home from its floor area, using the property settings above. Less accurate than the room-by-room option.
Your heating system temperatures
Used for the “Your system” radiator rating. Many condensing boilers run around 55/45; a heat pump usually runs cooler. Check your own settings.
Boiler & Radiator Sizing Calculator UK
Use this boiler and radiator sizing calculator to estimate how much heat a room or a whole home loses on a cold design day. It shows the result in watts and BTU per hour, the catalogue radiator rating you would need at different flow temperatures, and a starting range for boiler output. It follows the same building blocks as a professional heat-loss calculation, using published UK default data, but it is a homeowner’s estimate and not a heat-loss survey.
How to use the calculator
- Pick your location. This sets the design outside temperature. Add your height above sea level if you live somewhere high.
- Describe the property. Choose the wall type, glazing, how draughty the home is, and its age band for thermal bridging.
- Choose a mode. Use One room to size radiators, Whole house, room by room for a full estimate, or Quick estimate if you only know the floor area.
- Enter your flow and return temperatures to see a radiator rating for your own system.
- Press Calculate. Changing inputs afterwards updates the result.
Design temperatures used
Room temperatures follow the internal design temperatures in the MCS heat pump design standard (MIS 3005-D, issue 3.0, December 2025), which draws them from CIBSE guidance: living, dining and bedsitting rooms 21 °C; bedrooms, kitchens, halls and landings, and toilets 18 °C; bathrooms 22 °C. You can edit any room temperature.
Outside design temperatures are the 99.6% values from CIBSE Guide A Table 2.5 for 14 UK sites, as listed in the MCS Heat Load Calculator reference documentation. For every whole 100 m that your property is above the reference site’s altitude, this tool lowers the design temperature by 0.6 °C, as that documentation describes.
| Location | Design outside temperature (99.6%) |
|---|---|
| Belfast | −3.2 °C |
| Birmingham | −5.1 °C |
| Cardiff | −3.1 °C |
| Edinburgh | −5.4 °C |
| Glasgow | −5.6 °C |
| Leeds | −3.3 °C |
| London | −3.0 °C |
| Manchester | −4.5 °C |
| Newcastle | −3.7 °C |
| Norwich | −4.6 °C |
| Nottingham | −3.9 °C |
| Plymouth | −1.5 °C |
| Southampton | −4.8 °C |
| Swindon | −4.6 °C |
Figures checked 28 September 2026. London is -3.0 °C, so the familiar -3 °C figure is a London-style value and not a UK-wide one.
U-values used
Wall, roof and floor defaults come from the RdSAP 10 specification (BRE, June 2025), the method used for EPCs on existing homes. Wall values are the England table; the Scotland, Wales and Northern Ireland tables differ for some newer build ages. Real walls vary, so if you know your actual U-value from a survey or EPC, it is better than these defaults.
| Element | U-value (W/m²K) | Basis |
|---|---|---|
| Solid brick or stone wall, uninsulated | 1.7 | RdSAP 10 defaults for a typical solid wall |
| Solid wall with about 100 mm insulation | 0.30 | Calculated using the RdSAP 10 method for added insulation |
| Cavity wall, before 1976, unfilled / filled | 1.5 / 0.7 | RdSAP 10 England table |
| Cavity wall, 1976-1982 / 1983-1995 / 1996-2002 | 1.0 / 0.60 / 0.45 | RdSAP 10 England table |
| Cavity wall, 2003-2006 / 2007-2011 / 2012-2022 / 2023+ | 0.35 / 0.30 / 0.28 / 0.26 | RdSAP 10 England table |
| Loft insulation: none / 100 / 150 / 200 / 270 / 300 mm | 2.3 / 0.40 / 0.30 / 0.21 / 0.16 / 0.14 | RdSAP 10 roof table for insulation at joists |
| Flat roof: uninsulated / built 2012-2022 | 2.3 / 0.18 | RdSAP 10 assumed roof values |
| Solid ground floor: uninsulated / 50 mm / 100 mm | 0.77 / 0.35 / 0.23 | RdSAP 10 floor method for a representative 6 m by 8 m footprint (illustrative) |
| Suspended timber floor: uninsulated / 100 mm | 0.78 / 0.24 | RdSAP 10 floor method for the same footprint (illustrative) |
| Floor over an unheated garage or passage | 1.2 | RdSAP 10 exposed floor value, uninsulated |
| Single glazing | 4.8 | RdSAP 10 default for a wooden frame, as reproduced by EPC Works |
| Double glazing before 2002 or unknown age | 2.8 | CIBSE domestic heating design guide value, as used in MCS documentation |
| Double glazing 2002-2021 / 2022 onwards | 2.0 / 1.4 | RdSAP 10 defaults, as reproduced by EPC Works |
| Triple glazing, modern | 1.0 | Engineering assumption; use your window rating if you have it |
| Solid external door | 3.0 | CIBSE domestic heating design guide value, as used in MCS documentation |
Figures checked 28 September 2026 against the sources listed below. Ground floors: for a solid floor the temperature difference is the room temperature minus 10 °C (an assumed annual mean ground temperature); for a suspended floor it is the room temperature minus the outside design temperature, following MIS 3005-D.
Ventilation and thermal bridging
Ventilation loss is 0.33 W per cubic metre per kelvin for each air change per hour. The three draughtiness settings (0.5, 0.8 and 1.5 air changes per hour) are engineering assumptions. The lowest matches the CIBSE minimum room rate used in MCS documentation; 0.8 is close to the effective rate reported for older, naturally ventilated homes when the full BS EN 12831 ventilation method is used. Choosing a higher rate raises the result, and the right value for your home is uncertain.
Thermal bridging is added using the RdSAP 10 factor (0.15 W/m²K for homes built before 2003, 0.11 for 2003-2006 and 0.08 for 2007 onwards) applied to the exposed area. You can switch it off.
Radiator size and delta T
Radiator manufacturers publish outputs at delta T 50 under BS EN 442, for example 75/65 °C flow and return in a 20 °C room. At a lower delta T the radiator gives out less. This calculator uses the common relationship output × (delta T / 50)1.3, with an exponent of 1.3 that manufacturers describe as representative of most radiators. Column and towel radiators can differ, so use the manufacturer’s own figures when they are available.
| Delta T | Example flow/return (20 °C room) | Output compared with catalogue | Rating needed compared with the room’s heat loss |
|---|---|---|---|
| 50 K | 75/65 °C | 100% | 1.00 times |
| 40 K | 65/55 °C | 75% | 1.34 times |
| 30 K | 55/45 °C | 51% | 1.94 times |
| 22.5 K | 45/40 °C (heat pump style) | 35% | 2.82 times |
Worked example
Take a 4.5 m by 3.5 m living room, 2.4 m high, with one 4.5 m external wall containing a 2.5 m² window. The walls are cavity (built 1983-1995), the glazing is double (2002-2021), the floor is solid and uninsulated, there is a heated room above, and the home is in London at -3.0 °C outside with the room at 21 °C, typical draughtiness and a 0.15 thermal bridging factor. The calculator estimates roughly 708 W (about 2,415 BTU/hr). A radiator running at delta T 50 would need a catalogue rating of about 708 W, at delta T 40 about 946 W and at delta T 30 about 1,375 W. This is an illustration of the method, not a recommendation for your home.
Boiler sizing: what this calculator does and does not do
For the whole-house modes, the total of the room heat losses is your design space-heating load. The suggested boiler range runs from that load up to 20% above it, rounded to the nearest half kilowatt. The 20% is an engineering assumption for uncertainty in the inputs, not an official rule.
- No hot water is included. Combi boiler output is normally driven by hot water flow, which is a separate assessment.
- Oversizing is a risk. A boiler well above the load may short-cycle. Check the manufacturer’s minimum modulated output against your load.
- Get it checked. For gas appliances in Great Britain the installer must be Gas Safe registered. Ask for a room-by-room heat-loss calculation before you commit.
- Heat pumps need more. MCS requires the installer to complete a full BS EN 12831-1 heat load calculation for a heat pump design. Use this tool only for a rough first idea.
What is not included
- Heat gains from people, appliances, hot water pipework and the sun are not deducted.
- Internal walls are assumed to lose no heat, so neighbouring rooms are assumed to be heated. An unheated neighbouring property or room would add to the real load.
- Party walls, conservatories, basements and rooms in the roof are not modelled. Enter a custom-sized room using the closest options, or ask an installer.
- Radiator sizes are a minimum catalogue rating, not a product recommendation.
Frequently Asked Questions
How many BTU do I need to heat a room?
It depends on the room’s heat loss, not just its size. This calculator adds up the heat lost through the walls, windows, doors, roof or ceiling, floor and ventilation at the design temperature difference, then converts watts to BTU per hour (1 W = 3.412 BTU/hr). A well-insulated room can need far fewer BTU than a similar-sized uninsulated one, so a simple BTU-per-square-metre rule of thumb can be a poor guide.
What does radiator delta T (ΔT50, ΔT40, ΔT30) mean?
Delta T is the mean water temperature in the radiator minus the room temperature. Catalogue outputs are published at delta T 50 (for example 75/65 °C flow and return in a 20 °C room). At a lower delta T a radiator gives out less heat, roughly following (delta T / 50) to the power of 1.3 for many radiators, so it needs a higher catalogue rating to deliver the same watts. Use the manufacturer’s own data where it is published.
Does this calculator size a combi boiler?
No. It estimates space-heating load only and does not add any hot water allowance. Boiler choice also depends on hot water demand, system type (combi, system or regular) and an installer’s assessment. The output range shown is a starting point for a conversation with a qualified installer, not a purchase specification.
Why does the design outside temperature change with location?
Design temperatures are set for the cold conditions a heating system is expected to handle. This tool uses the 99.6% values from CIBSE Guide A, as reproduced in MCS heat load guidance, for 14 UK locations, with an optional altitude correction. London is -3.0 °C, so -3 °C is a London-style figure rather than a UK-wide one. Choose the nearest location or enter your own figure.
Can I use this to size a heat pump?
Not for an installation. MCS heat pump design requires a room-by-room heat load calculation to BS EN 12831-1 by the installer. This calculator can give you a rough idea of your heat loss before you talk to installers, but it should not be used to specify a heat pump.
Is a bigger boiler or bigger radiators always better?
No. An oversized boiler can short-cycle, and oversized equipment adds cost without improving comfort. Radiators sized to each room’s heat loss at your intended flow temperature help a system run at lower temperatures. The best answer comes from a proper room-by-room calculation.
Why is my result different from a rule of thumb or another calculator?
Results depend heavily on assumed U-values, air change rates and design temperatures, which differ between tools and can differ from your actual home. This calculator states its assumptions and uses published default U-values from RdSAP 10 where available. Treat the result as an estimate and check the assumptions listed with your results.
How accurate is this calculator?
It is an estimate. Default U-values, ventilation rates and design temperatures are assumptions, and real homes vary in construction, airtightness, neighbouring properties, solar and internal gains and how the heating is controlled. A qualified engineer’s room-by-room calculation with measured details will be more reliable.
Does this apply in Scotland, Wales and Northern Ireland?
The method and design temperatures are UK-wide references, but the default wall U-values follow the England table in RdSAP 10. The Scotland, Wales and Northern Ireland tables differ for some newer build ages, and Building Regulations differ by nation. Check the rules that apply where you live.
Sources
- MCS MIS 3005-D: The Heat Pump Standard (Design), issue 3.0 – internal design temperatures and floor temperature difference rules.
- MCS Heat Load Calculator: design conditions – CIBSE Guide A outside design temperatures and the altitude correction.
- MCS Heat Load Calculator: U-values – glazing and door values from the CIBSE domestic heating design guide.
- BRE RdSAP 10 specification, June 2025 – default wall, roof and floor U-values, floor calculation method and thermal bridging factors.
- EPC Works: glazing – a reproduction of RdSAP 10 default window U-values.
- Zehnder UK: delta T correction factors – radiator exponent of 1.3 and delta T conversion.